Field calculators · iOS

Electrical
Pro Toolkit

1.0version
12calculators
4languages
IEC60364
NECNFPA 70
254unit tests
Andrei Neagoecreated by

A cable has two limits. Most tools check one.

A conductor has to carry its current without overheating, and hold the voltage drop within target over the run. These are independent limits, and which one governs flips depending on the job — short and heavy, thermal wins; long and light, the drop wins. Size against either alone and you will be wrong half the time.

Thermal capacity needs16 mm²
Voltage drop needs6 mm²

Both are shown. The larger one is what you install.

Voltage Drop Calculator result: 6.96% estimated drop, required minimum cable 16 mm² governed by current-carrying capacity, with a breakdown reading thermal capacity needs 16 mm² and voltage drop needs 6 mm².
Voltage Drop · the governing size and both constraints behind it

How it arrives at a size

Five steps, in this order, every time. The app shows the working next to the number rather than asking you to take it on faith.

01

You describe the installation, not just the load

Insulation, installation method, ambient temperature and how many circuits are bunched together. On a warm roof void with six circuits in one tray, these move the answer further than the current does.

02

Thermal axis — tabulated capacity, then the derating

The reference capacity for that size and method is multiplied by the ambient and grouping factors. Under NEC the derated result is then capped at the termination rating you selected, 60 °C or 75 °C, because the limit is usually the lug and not the cable — NEC 110.14(C).

03

Drop axis — resistance at operating temperature

Conductor resistivity is taken at normal service temperature, as IEC 60364-5-52 defines it: ρ = 1.25 × ρ₂₀, so copper enters the calculation at κ = 44.8 rather than the 20 °C figure of 56. Computing a hot cable with cold-copper numbers understates the drop by 20%.

04

The governing size is the larger of the two

Each axis produces a required area independently. The result is whichever is bigger, stepped up to the next real size — mm² on IEC, AWG and kcmil on NEC — and labelled with which axis governed it.

05

If it cannot be met, it says so

When no size in the table can carry the load, or none holds the drop target, the app reports that exhaustion rather than quietly returning the largest row. A constraint that could not be satisfied never renders as one that was.

Voltage Drop Calculator inputs: current, cable length, conductor sizing switched between mm² and AWG, voltage with 230, 240 and 110 volt presets, copper or aluminium, 1-phase, 3-phase or DC, and a thermal conditions group with PVC or XLPE insulation and installation methods B1, B2, C and E.
Voltage Drop · inputs, with the thermal conditions in the same form

Step 01, on screen

Conductor material, system type, insulation, installation method, ambient and grouping all sit in the same form as the current and the length, because they all change the answer.

DC is a first-class system alongside 1-phase and 3-phase, and it carries no assumed nominal voltage. A 12 V bank and a 600 V string are both DC, so rather than pick one the percentage stays blank until you enter the actual bus voltage.

Every reference capacity can be overridden with the rating printed on your own cable's data sheet.

Yield from your coordinates, not from a rule of thumb

The one tool that reaches the network. The other eleven run entirely on the device.

Solar Estimator

Enter peak power and system loss, drop a pin or use your current position, and it queries PVGIS v5.2 — the European Commission's irradiation database — for that exact latitude and longitude.

You get annual production, a month-by-month breakdown you can tap for the figure behind each bar, and the optimal tilt and azimuth for the site. Azimuth follows the PVGIS convention where 0° is south.

System loss defaults to 14% and is yours to change. Nothing about your location is stored or sent anywhere except to PVGIS to answer the query.

Solar Estimator: 6 kWp peak power at 14% system loss returning 7639 kWh estimated yearly production, a monthly production bar chart from January to December, and optimal tilt 35 degrees with optimal azimuth 3 degrees.
Solar Estimator · monthly production, tap a bar for its value

Twelve tools, one grammar

Same shape on every screen: inputs at the top, the result in the middle, the assumptions underneath it. Nothing is hidden behind a menu.

Tools Dashboard listing Voltage Drop Calculator, Motor Sizing, Conduit Fill, Lighting, Short Circuit, Solar Estimator, Unit Converter and Ohm's Law as cards in a two-column grid.
Dashboard
Conduit Fill: measured internal diameter of 25 mm with 10.5 mm² per wire and three or more conductors, returning a maximum of 18 wires, with a note that it uses the 40 percent column of NEC Chapter 9 Table 1.
Conduit Fill · states its own method
Battery Bank: 5000 Wh daily load, 3 days autonomy, 48 V bank, lithium chemistry at 0.9 depth of discharge and 0.95 efficiency, returning 365 Ah required capacity and 17.54 kWh stored energy.
Battery Bank
Unit Converter set to the Power category, converting 74 kW to 99.2356 HP, with Energy, Temperature, Pressure and Length among the other categories.
Unit Converter · 12 categories
Settings: electrical standard switched between IEC Europe and NEC North America, language list of English, Español, Français and Deutsch, and an about panel reading Electrical Pro Toolkit version 1.0.0.
Settings · standard and language

Scroll for more →

What each one works out

Every calculator names the method it uses, on screen, next to the number.

Tools and their basis
CalculatorWhat it works outBasis
Voltage DropDrop across a run, 1-phase, 3-phase and DCIEC 60364
Cable AmpacityCapacity after ambient, grouping and install method60364-5-52 · 310.16
Motor SizingFull load amps, breaker, synchronous speedNEC 430
Short CircuitFault current at a transformer secondaryInfinite bus
Conduit FillConductors per conduit, measured ID or trade sizeCh. 9 T1 · T4
Earth ConductorProtective conductor, and EGC by device rating60364-5-54 · 250.122
Power FactorCapacitor bank in kVAr, and in µF at your frequencyQ = P(tanφ₁−tanφ₂)
LightingFixture count for a target illuminanceLumen method
PV String SizingModules per string inside the inverter windowIEC 62548
Solar YieldMonthly and annual production at your coordinatesPVGIS v5.2
Battery BankOff-grid capacity from load, autonomy and DoDAh = Wh ⁄ V
Ohm's LawV, I, R and P from any twoV = IR

Built for both sides of the Atlantic

One setting switches the whole app, not just the labels.

mm² / AWGConductor sizing, with kcmil
50 / 60 HzFeeds motor speed and capacitance
°C / °FDerating, ambient, cell temperatures
m / ftRuns, rooms, illuminance in lx or fc

What it will tell you that it doesn't know

A calculator that hides its assumptions is harder to trust than one that shows them.

It refuses rather than guesses

When no standard size can carry the load, or none meets the drop target, it says so and shows nothing. A missing constraint never renders as a satisfied one.

DC has no assumed voltage

A 12 V bank and a 600 V string are both DC. Rather than pick one, it leaves the percentage blank until you enter the actual bus voltage.

Reference tables are labelled as such

Built-in ampacities are convenience values, checked against published sources and marked where those sources disagree. Any of them can be overridden with the rating from your own cable.

It works where the job is

Eleven of the twelve run with no connection at all. No account, no sign-in, and nothing you type is sent anywhere.